MODEL |
CK-2 |
CK-3 |
CK-4 |
| Design
Standard * |
23°± 1°C DB 50% ± 2% RH |
| Total |
BTU/HR
(kW) |
22,800 (6.7) |
30,400 (8.9) |
45,600 (13.4) |
| Sensible |
BTU/HR
(kW) |
17,800 (5.9) |
23,700 (8.1) |
35,600 (11.8) |
| Air Flow |
CFM
(L/s) |
900 (425) |
1200 (566) |
1800 (850) |
| Reheat |
kW |
7.5 |
12 |
15 |
| Humidifier |
kW |
4 |
6 |
6 |

Environmental Module
|
| Compu-Air
model CK - # shall be a factory assembled and tested environmental conditioning module
including: |
 |
high
efficiency scroll compressor |
 |
water
cooled condenser and regulating valve |
 |
optional
remote condenser or condensing unit |
 |
upflow
discharge air supply |
 |
adjustable
belt drive DWDI blower |
 |
high
efficiency filters |
 |
fully
modulating electric reheat |
 |
fully
modulating electric humidifier |
 |
bulit-in
main disconnect and power panel |
|
|
Environmental Control System
|
| CTC
2000 factory assembled and tested: |
 |
powerful
setpoint programming capabilities |
 |
10
inch temperature and humidity recorder |
 |
high
intensity LED displays |
 |
prompt
messages |
 |
access
codes |
 |
high/low
temperature alarm |
 |
high/low
humidity alarm |
 |
self-diagnostics |
 |
digital
communication to supervisory computer via multidrop (RS232/RS422/RS485 ports) available |
|
Environmental Room (if required
Please refer to Environmental Rooms page

|